David J. Eaton
SDGE - San Diego Gas & Electric
UGM 2005
September 30 2004, 5:30AM
Flashover on a 500 kV line.
Line could not be re-energized until repairs were made.
Line was out of service for nine hours.
A rough estimate for the nine hour outage: $200,000-$400,000
Reasons for the flashover:
Dust contamination from rock crushing operation.
Exceptionally dry year due to 180 days without rain.
We were asked to fly a portion of this 83 mile line to determine
if we had any other contamination problems.
We easily identified four towers that needed cleaning.
Bird contamination was also building on the insulators.
Helicopter cost for the one hour flight, $550.00
176 towers were inspected in a one hour flight.
Four towers had extreme corona activity
Two of those towers needed to be hand wiped.